Inverter-Embedded Partial Discharge Testing for Reliability Enhancement of Stator Winding Insulation in Low Voltage Machines
- 13 January 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 58 (2) , 2088-2096
Abstract
Partial discharge (PD) due to high dv/dt pulsewidth modulation has been identified as one of the leading causes of insulation failure in low voltage (LV) variable frequency drive (VFD) fed motors with random wound stator windings. With the recent increase in electrical stress with faster risetime wide bandgap power semiconductor devices and higher dc link voltage for higher efficiency and power density of the system, PD-induced insulation failures are expected to increase. Since LV motor insulation is not resistant to PD, an increasing number of VFD motors are being qualified for PD-free operation. However, the PD inception voltage of qualified motors decreases with insulation aging making LV motors susceptible to failure. In this article, an offline standstill test method is proposed for automated inverter-embedded PD testing under impulse excitation. The main concept is to perform the impulse PD test using the VFD at increased voltage levels for providing advanced warning of PD activity for preventing forced outage of VFD motors. Options for application of increased impulse test voltage and automated detection of PD for implementing the proposed concept are presented. Testing on an 800 V VFD driven motor shows that the proposed method can provide automated impulse PD testing whenever the motor is at standstill to warn the end user of impending PD activity that can lead to failure.Keywords
Funding Information
- National Research Foundation of Korea
- Ministry of Science and ICT, South Korea (NRF-2019R1A2C1084104)
This publication has 18 references indexed in Scilit:
- Evaluation and Current-Response-Based Identification of Insulation Degradation for High Utilized Electrical Machines in Railway ApplicationIEEE Transactions on Industry Applications, 2017
- Impact of SiC semiconductors switching transition speed on insulation health state monitoring of traction machinesIET Power Electronics, 2016
- Qualification of Hairpin Motors Insulation for Automotive ApplicationsIEEE Transactions on Industry Applications, 2016
- Partial discharge in electric motor fed by a PWM inverter: off-line and on-line detectionIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Turn-to-turn capacitance variations correlated to PDIV for AC motors monitoringIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Experimental evaluation of using the surge PD test as a predictive maintenance tool for monitoring turn insulation quality in random wound AC motor stator windingsIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Monitoring off-line and on-line PD under impulsive voltage on induction motors - part 1: standard procedureIEEE Electrical Insulation Magazine, 2010
- A UHF Technique for Advanced PD Measurements on Inverter-Fed MotorsIEEE Transactions on Power Electronics, 2008
- An Advanced Stator Winding Insulation Quality Assessment Technique for Inverter-Fed MachinesIEEE Transactions on Industry Applications, 2008
- Partial-discharge-inception testing on low-voltage motorsIEEE Transactions on Industry Applications, 2006