Load Frequency Control of Photovoltaic Generation-Integrated Multi-Area Interconnected Power Systems Based on Double Equivalent-Input-Disturbance Controllers
Open Access
Abstract
With the rapid increase of photovoltaic (PV) penetration and distributed grid access, photovoltaic generation (PVG)-integrated multi-area power systems may be disturbed by more uncertain factors, such as PVG, grid-tie inverter parameters, and resonance. These uncertain factors will exacerbate the frequency fluctuations of PVG integrated multi-area interconnected power systems. For such system, this paper proposes a load frequency control (LFC) strategy based on double equivalent-input-disturbance (EID) controllers. The PVG linear model and the multi-area interconnected power system linear model were established, respectively, and the disturbances were caused by grid voltage fluctuations in PVG subsystem and PV output power fluctuation and load change in multi-area interconnected power system. In PVG subsystems and multi-area interconnected power systems, two EID controllers add differently estimated equivalent system disturbances, which has the same effect as the actual disturbance, to the input channel to compensate for the impact of actual disturbances. The simulation results in MATLAB/Simulink show that the frequency deviation range of the proposed double EID method is 6% of FA-PI method and 7% of conventional PI method, respectively, when the grid voltage fluctuation and load disturbance exist. The double EID method can better compensate for the effects of external disturbances, suppress frequency fluctuations, and make the system more stable.Keywords
Funding Information
- National Natural Science Foundation of China (61973322)
This publication has 42 references indexed in Scilit:
- LFC for multi‐area interconnected power system concerning wind turbines based on DMPCIET Generation, Transmission & Distribution, 2017
- Impact of High PV Penetration on the Inter-Area Oscillations in the U.S. Eastern InterconnectionIEEE Access, 2017
- Load frequency controller design of a two-area system composing of PV grid and thermal generator via firefly algorithmNeural Computing and Applications, 2016
- The sliding mode load frequency control for hybrid power system based on disturbance observerInternational Journal of Electrical Power & Energy Systems, 2016
- Active power control of solar PV generation for large interconnection frequency regulation and oscillation dampingInternational Journal of Energy Research, 2015
- Intelligent photovoltaic farms for robust frequency stabilization in multi-area interconnected power system based on PSO-based optimal Sugeno fuzzy logic controlRenewable Energy, 2015
- The Impact of Increased Penetration of Converter Control-Based Generators on Power System Modes of OscillationIEEE Transactions on Power Systems, 2014
- Small Signal Stability Assessment of Power Systems With Increased Penetration of Photovoltaic Generation: A Case StudyIEEE Transactions on Sustainable Energy, 2013
- System Stability Impact of Large-Scale and Distributed Solar Photovoltaic Generation: The Case of Ontario, CanadaIEEE Transactions on Sustainable Energy, 2013
- Impact of increased penetration of photovoltaic generation on power systemsIEEE Transactions on Power Systems, 2012