Due to the complicated working environment of dry hollow shunt reactors, the existing detection methods are difficult to conduct accurate fault detection. The circuit model of dry air-core shunt reactors is established, and the branch current calculation method of normal working reactors and fault reactors is given. Taking BKDK-20000/35 dry hollow shunt reactors as an example, the variation regularity of branch current under inter-turn short-circuit fault is analyzed. Proposed by measuring the branch current method to determine the dry hollow shunt reactor defects. The reactor's own magnetic field model is established, and the magnetic field model is calculated by analytic method and ANSYS software respectively. The model of inter-frequency interference between operating reactor and the reactor under test is established to analyze the magnetic field generated by the working reactor. The influence of other magnetic fields on the branch current measurement of inter-turn short-circuit reactors is also discussed. The research results show that, when the inter-turn short circuit fault occurs to dry-type air-core shunt reactor, the total current of reactor changes little and the variation of distributed current is obvious near the fault location. By detecting the branch current, it can be judged whether the reactor has the inter-turn short circuit fault. The influence of power frequency interference caused by running reactor on branch current measurement should not be neglected. The larger magnetic field in the substation is located near the reactor. The magnitude of the magnetic induction of other magnetic fields in the space is related to the layout of the device and the size of the current, and its influence is relatively small.