Analysis of Gas Generated in Mineral Oil, Synthetic Ester, and Natural Ester as a Consequence of Thermal Faults
Open Access
- 20 May 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 7, 65040-65051
Abstract
The gases generated by electrical and thermal faults are similar in the case of mineral oil, synthetic ester, and natural ester. However, there are considerable differences in the amount of the generated gases and their solubility in these liquids, what should be taken into account during power transformer diagnostics by means of dissolved gas analysis (DGA) method. The aim of the research was to compare the gases generated as a result of thermal faults (250°aC, 350°C and 450°C) in mineral oil and both esters. The following gases were analyzed: hydrogen, methane, ethane, ethylene, acetylene, propane, propylene, carbon oxide, and carbon dioxide. A qualitative and quantitative analysis of these gases were carried out by means of gas chromatography. A large share of propane in the sum of the gases generated in the esters, mainly in the synthetic ester, was found. Propane and propylene in most of gas interpretation approaches are omitted. The authors proved that in the case of synthetic ester the using of propane as the key gas for thermal faults detection is justified. The obtained results can be used to improve the interpretation of DGA results, in the case of ester liquids used in power transformers.Keywords
Funding Information
- Ministerstwo Nauki i Szkolnictwa Wyższego (04/41/DS-PB/4345, 04/41/DS-PB/4391)
This publication has 22 references indexed in Scilit:
- Comparison of Dissolved Gases in Mineral and Vegetable Insulating Oils under Typical Electrical and Thermal FaultsEnergies, 2016
- Compare the performance of natural ester with synthetic ester as transformer insulating oil2015
- Study about stray gas generation in transformer oil at different temperatures2014
- DGA comparison between ester and mineral oilsIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Dissolved gas analysis investigations on ester liquids after breakdown2011
- Dissolved gas analysis of alternative dielectric fluids under thermal and electrical stress2011
- DGA comparison between ester and mineral oils2011
- The duval triangle for load tap changers, non-mineral oils and low temperature faults in transformersIEEE Electrical Insulation Magazine, 2008
- Dissolved gas analysis of alternative fluids for power transformersIEEE Electrical Insulation Magazine, 2007
- Vegetable oils for liquid-filled transformersIEEE Electrical Insulation Magazine, 2002