Abstract
Frequency response analysis (FRA) is a usual method for diagnosing winding, core, insolation faults in transformer. By the change of the FRA traces, the faults can be detected. This study presents the interpretation on influence of untested winding's fault. A special power transformer of rating 10 kV/400 V, three‐phase, 50 Hz, YNyn0 has been developed for carrying out FRA tests by practically simulated various winding faults in different phase. The windings of phase ‘A’ and phase ‘B’ on HV side are tested with different types of faults, respectively. The results of these experiments are displayed and discussed. It shows that when the untested winding is shorted, the influence of the inductive fault can be eliminated.Keywords
Funding Information
- National Natural Science Foundation of China (51377175)
This publication has 10 references indexed in Scilit:
- Influence of temperature and moisture content on frequency response analysis of transformer windingIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Understanding power transformer frequency response analysis signaturesIEEE Electrical Insulation Magazine, 2013
- Frequency response analysis and short-circuit impedance measurement in detection of winding deformation within power transformersIEEE Electrical Insulation Magazine, 2013
- Power Transformer Economic Evaluation in Decentralized Electricity MarketsIEEE Transactions on Industrial Electronics, 2011
- Case studies of factors influencing frequency response analysis measurements and power transformer diagnosticsIEEE Electrical Insulation Magazine, 2011
- The Influence of Complex Permeability on the Broadband Frequency Response of a Power TransformerIEEE Transactions on Power Delivery, 2009
- Frequency response analysis- condition assessment of power transformers using mathematical and statistical criteria2009
- Effect of Core Magnetization on Frequency Response Analysis (FRA) of Power TransformersIEEE Transactions on Power Delivery, 2008
- Sweep frequency response analysis (SFRA) for the assessment of winding displacements and deformation in power transformersElectric Power Systems Research, 2008
- Monitoring of power transformers using the transfer function methodIEEE Transactions on Power Delivery, 1999