Highly Sensitive and Selective Acetylene CuO/ZnO Heterostructure Sensors through Electrospinning at Lean O2 Concentration for Transformer Diagnosis

Authors:

Abstract
Acetylene (C2H2) is a gas that can cause explosions in transformers even at low concentrations. Gas chromatography (GC) or photoacoustic spectroscopy (PAS) have been used to detect C2H2 during dissolved gas analysis (DGA), but they are not suitable for monitoring numerous transformers at substations. Even though metal oxide semiconductor (MOS) based C2H2 sensors have drawn much attention as a potential solution, existing MOS-based C2H2 sensors have low sensitivity toward C2H2 in the transformer environment (10 h). In addition, the CZ2 sensor also shows a high selectivity (>5 times) to coexisting transformer oil gases which are H2, CH4, C2H4, C2H6, CO, and CO2. Overall, this study is the first to demonstrate a high performing DGA sensor under 2% O2 concentration that can provide a practical solution to monitoring the low concentration of C2H2 in transformers effectively.
Funding Information
  • KEPCO Research Institute (R23XA01)
  • Korea Technology and Information Promotion Agency for SMEs (RS-2022-00165292)
  • Korea Evaluation Institute of Industrial Technology (RS-2022-00154820)

This publication has 45 references indexed in Scilit: