Low-voltage ride-through capability improvement of Type-3 wind turbine through active disturbance rejection feedback control-based dynamic voltage restorer
Open Access
- 1 October 2023
- journal article
- research article
- Published by Oxford University Press (OUP) in Clean Energy
- Vol. 7 (5) , 1091-1109
Abstract
Disconnections due to voltage drops in the grid cannot be permitted if wind turbines (WTs) contribute significantly to electricity production, as this increases the risk of production loss and destabilizes the grid. To mitigate the negative effects of these occurrences, WTs must be able to ride through the low-voltage conditions and inject reactive current to provide dynamic voltage support. This paper investigates the low-voltage ride-through (LVRT) capability enhancement of a Type-3 WT utilizing a dynamic voltage restorer (DVR). During the grid voltage drop, the DVR quickly injects a compensating voltage to keep the stator voltage constant. This paper proposes an active disturbance rejection control (ADRC) scheme to control the rotor-side, grid-side and DVR-side converters in a wind–DVR integrated network. The performance of the Type-3 WT with DVR topology is evaluated under various test conditions using MATLAB®/Simulink®. These simulation results are also compared with the experimental results for the LVRT capability performed on a WT emulator equipped with a crowbar and direct current (DC) chopper. The simulation results demonstrate a favourable transient and steady-state response of the Type-3 wind turbine quantities defined by the LVRT codes, as well as improved reactive power support under balanced fault conditions. Under the most severe voltage drop of 95%, the stator currents, rotor currents and DC bus voltage are 1.25 pu, 1.40 pu and 1.09 UDC, respectively, conforming to the values of the LVRT codes. DVR controlled by the ADRC technique significantly increases the LVRT capabilities of a Type-3 doubly-fed induction generator-based WT under symmetrical voltage dip events. Although setting up ADRC controllers might be challenging, the proposed method has been shown to be extremely effective in reducing all kinds of internal and external disturbances.Keywords
This publication has 42 references indexed in Scilit:
- An improved low-voltage ride-through performance of DFIG based wind plant using stator dynamic composite fault current limiterISA Transactions, 2016
- Full converter based wind turbine generator system generic modelling: Variations and applicabilitySustainable Energy Technologies and Assessments, 2016
- Comparison among series compensators for transient stability enhancement of doubly fed induction generator based variable speed wind turbinesIET Renewable Power Generation, 2016
- Transient Reconfiguration and Coordinated Control for Power Converters to Enhance the LVRT of a DFIG Wind Turbine With an Energy Storage DeviceIEEE Transactions on Energy Conversion, 2015
- The Use of Averaged-Value Model of Modular Multilevel Converter in DC GridIEEE Transactions on Power Delivery, 2014
- Troubleshooting a digital repetitive controller for a versatile dynamic voltage restorerInternational Journal of Electrical Power & Energy Systems, 2014
- Dynamic performance of average-value models for multi-terminal VSC-HVDC systems2012
- Ride Through of Wind Turbines With Doubly Fed Induction Generator Under Symmetrical Voltage DipsIEEE Transactions on Industrial Electronics, 2009
- Control of a Doubly Fed Induction Generator in a Wind Turbine During Grid Fault Ride-ThroughIEEE Transactions on Energy Conversion, 2006
- Compensation voltage control in dynamic voltage restorers by use of feed forward and state feedback schemeIEEE Transactions on Power Electronics, 2005