Evaluation of flashover voltage property of snow accreted insulators for overhead transmission lines, part III - 154 kv full-scale flashover voltage test of snow accreted insulators -
Authors:
- 1 December 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 21 (6) , 2568-2575
Abstract
In December 2005, Japan experienced a major outage in Niigata Kaetsu area due to a large amount of wet snow mixed with sea-salt accreted on several transmission line insulators. To clarify the causes of the snow-induced outage and increase reliability of the networks, a 154 kV class full-scale snow test procedure to evaluate various insulator designs was developed, and artificial flashover voltage tests of snow accreted insulators were carried out. High voltage flashover tests showed that the flashover voltage of both long-rod and cap & pin insulators was decreased with the increase of snow conductivity. Also, cap & pin insulators showed significantly higher flashover voltage than long-rod insulators. Thus substitution of long-rod insulators with cap & pin insulators appears to be reasonable as a countermeasure against snow induced flashovers.Keywords
This publication has 10 references indexed in Scilit:
- Icing Flashovers2009
- Laboratory Tests and Web Based Surveillance to Determine the Ice- and Snow Performance of InsulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2007
- Investigation of Flashover Performance of Snow-Covered BreakersIEEE Transactions on Dielectrics and Electrical Insulation, 2007
- Selection of Line Insulators With Respect to Ice and Snow—Part II: Selection Methods and Mitigation OptionsIEEE Transactions on Power Delivery, 2007
- Selection of Line Insulators With Respect to Ice and Snow—Part I: Context and StressesIEEE Transactions on Power Delivery, 2007
- Selection of Station Insulators With Respect to Ice and Snow—Part I: Technical Context and Environmental ExposureIEEE Transactions on Power Delivery, 2005
- Selection of Station Insulators With Respect to Ice and Snow—Part II: Methods of Selection and Options for MitigationIEEE Transactions on Power Delivery, 2005
- AC withstand voltage characteristics of insulator string covered with snowIEEE Transactions on Power Delivery, 1988
- Performance of Insulators Covered With Snow or IceIEEE Transactions on Power Apparatus and Systems, 1979
- Flashover Tests of Insulators Covered with Ice or SnowIEEE Transactions on Power Apparatus and Systems, 1978