Modelica-Based Dynamic Modeling of a Chilled-Water Cooling Coil
Authors:
- Pengfei LiPLPengfei Li
- 1 January 2010
- journal article
- research article
- Published by Taylor & Francis in HVAC&R Research
- Vol. 16 (1) , 35-58
Abstract
For heating, ventilating, and air-conditioning (HVAC) systems for commercial buildings, the cooling coils in air-handling units (AHUs) account for a significant fraction of total building energy consumption and have a major impact on comfort conditions and maintenance costs. Development of cost-effective advanced control strategies will enhance the performance and efficiency of AHUs. The control design process can be greatly facilitated with simulation on a high-fidelity dynamic model prior to experimental validation and implementation. This paper presents a dynamic model for a chilled-water cooling coil. The model development was based on Dymola and Air Conditioning Library with some revision on heat exchanger modeling. For chilled-water cooling coil modeling, the major challenges include the variation of coil surface conditions under flow rate changes and partially-dry-partially-wet operations. This study proposes a dynamic coil model that is capable of predicting cooling performances under fully dry, partially-dry-partially-wet, and fully wet conditions. Validation with experimental data from a benchmark study was conducted under both dry and wet surface conditions. The model predicted the experimental results quite well for both transient and steady-state behaviors. Such a transient model will lay a more quality foundation for controller validation at the simulation phase.Keywords
This publication has 16 references indexed in Scilit:
- Transient behaviour of crossflow heat exchangers due to perturbations in temperature and flowInternational Journal of Heat and Mass Transfer, 2006
- Transient Behavior of Crossflow Heat Exchangers With Longitudinal Conduction and Axial DispersionJournal of Heat Transfer, 2004
- Mechanistic model of centrifugal chillers for HVAC system dynamics simulationBuilding Services Engineering Research & Technology, 2000
- The IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and SteamJournal of Engineering for Gas Turbines and Power, 2000
- A general dynamic simulation model for evaporators and condensers in refrigeration. Part I: moving-boundary formulation of two-phase flows with heat exchangeInternational Journal of Refrigeration, 1998
- Performance of Plate Finned Tube Heat Exchangers Under Dehumidifying ConditionsJournal of Heat Transfer, 1997
- A dynamical model adequate for controlling the evaporator of a heat pumpInternational Journal of Refrigeration, 1994
- Transient Response of Crossflow Heat Exchangers With Finite Wall CapacitanceJournal of Heat Transfer, 1992
- Transient Temperature Fields in Crossflow Heat Exchangers With Finite Wall CapacitanceJournal of Heat Transfer, 1988
- An Alternative Implementation of Variable Step-Size Multistep Formulas for Stiff ODEsACM Transactions on Mathematical Software, 1980