Feasibility Study of Ground Source Heat Pump System Considering Underground Thermal Properties
Open Access
Abstract
: A typical ground source heat pump (GSHP) system in South Korea has a ground heat exchanger (GHX) with a length of 100–150 m, which utilizes annually stable underground temperature to meet the loads of cooling, heating and hot water in buildings. However, most GSHP systems have been introduced in heating dominated areas because the system performance advantage is larger compared with air source heat pump system than that in cooling dominated areas. To effectively provide geothermal energy to the building in the limited urban area, it is necessary to install deep GHXs. Despite its large capacity, there are few studies on GSHP system with deep GHX over 300 m. In this study, to estimate the performance of the GSHP system with deep GHX and evaluate its feasibility, numerical simulation was conducted. To quantitatively analyze heat transfer between soil and GHX, the coupled model with GHX model and ground heat and groundwater transfer model was used. Furthermore, the heat exchange rate and the source temperature were calculated according to the operation modes, the length of GHX, and soil conditions such as geothermal gradient and thermal conductivity. As a result, the total heat exchange rate of GHX with a length of 300 m heat exchanger was 12.62 kW, 173% that of a length of 150 m. Finally, it was found that the GSHP system with deep GHX has realistic possibility in good condition of geothermal gradient.Keywords
Funding Information
- Korea Institute of Energy Technology Evaluation and Planning (20163030111350)
- Korea Institute of Geoscience and Mineral Resources (-)
This publication has 18 references indexed in Scilit:
- Numerical simulation of ground source heat pump systems considering unsaturated soil properties and groundwater flowApplied Thermal Engineering, 2018
- Technologies and environmental impacts of ground heat exchangers in FinlandGeothermics, 2018
- Methodology for energy strategy to prescreen the feasibility of Ground Source Heat Pump systems in residential and commercial buildings in the United StatesEnergy Strategy Reviews, 2017
- Thermal evaluation of coaxial deep borehole heat exchangersRenewable Energy, 2016
- Heat transfer analysis of a vertical ground heat exchanger using numerical simulation and multiple regression modelEnergy and Buildings, 2016
- Study on Heat Transfer Calculation Method of Ground Heat Exchangers Based on Heat Pump Unit Operation CharacteristicsProcedia Engineering, 2016
- Analysis of Earth Design Parameter and Geothermal Heat Exchanger Length in Geothermal SystemTransactions of the Korea Society of Geothermal Energy Engineers, 2015
- Thermal performance of a deep borehole heat exchanger: Insights from a synthetic coupled heat and flow modelGeothermics, 2015
- Combined simulation of a deep ground source heat exchanger and an office buildingBuilding and Environment, 2014
- Predicting the fluid temperature at the exit of the vertical ground heat exchangersApplied Energy, 2009