Improving the Error of Time Differences of Arrival on Partial Discharges Measurement in Gas-Insulated Switchgear
Open Access
Abstract
Partial Discharge (PD) detection based on Ultra-High-Frequency (UHF) measurements in Gas-Insulated Switchgear (GIS) is often used for fault location based on extraction of Time Differences of Arrival (TDoA), and the core technique is to obtain the precise time difference of each UHF signal. Usually, TDoA extraction algorithms can be categorized as cross-correlation function method (CCF), minimum energy method (ME), and threshold value method (TV) are not qualified to analyze the time difference with high accuracy and efficiency, especially the complicated UHF PD signals in the field. In this paper, multiple tests were carried out based on the real GIS UHF signals. Three typical algorithms (CCF, ME, and TV) were used to extract and calculate the TDoA of UHF signals. Afterwards, depending on the disassembly of equipment, the accuracy and effective range of the algorithms are analyzed by means of error and variance. To minimize the error and the variance, an average method with the combination (CA) and portfolio of traditional algorithms is proposed and verified in different situations. The results demonstrate that the improved algorithm could increase the accuracy of time difference extraction, less than 4.0%.Keywords
Funding Information
- Natural Science Foundation of Jiangsu Province (BK20170786)
- State Grid Zhejiang Electric Power Co. LTD. (5211DS17001C)
This publication has 20 references indexed in Scilit:
- Radio location of partial discharge sources: a support vector regression approachIET Science, Measurement & Technology, 2018
- Denoising of UHF PD signals based on optimised VMD and wavelet transformIET Science, Measurement & Technology, 2017
- Method for partial discharge localisation in air‐insulated substationsIET Science, Measurement & Technology, 2017
- Application of UHF sensors for PD measurement at power transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Study on the Partial Discharge Characteristics and Development Process in Use of the Multiple Discharge Patterns for the Typical Defects in Gas-Insulated SwitchgearCanadian Journal of Electrical and Computer Engineering, 2016
- PD Source Diagnosis and Localization in Industrial High-Voltage Insulation System via Multimodal Joint Sparse RepresentationIEEE Transactions on Industrial Electronics, 2016
- New aspects of UHF PD diagnostics on gas-insulated systemsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Location of PDs inside transformer windings using UHF methodsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Understanding the partial discharge activity generated due to particle movement in a composite insulation under AC voltagesInternational Journal of Electrical Power & Energy Systems, 2013
- Location of PD sources in power transformers by UHF and acoustic measurementsIEEE Transactions on Dielectrics and Electrical Insulation, 2012