Ground Fault Distance Protection for Paralleled Transmission Lines
Authors:
- 24 March 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 51 (6) , 5228-5236
Abstract
Paralleled transmission lines on the same tower can increase the power transmission capacity but bring challenges to the protection unit. The conventional distance protection schemes can easily be influenced and malfunction. This paper investigated the most commonly occurred ground fault scenarios and proposed two first zone distance protection schemes based on the measurement from only the single line of one terminal for single-phase ground faults and cross-country ground faults separately. A 500 kV and 300 mk parallel transmission testing system was built in the PSCAD/EMTDC with the parameters referring to a real operating site. The results derived from the simulation show that the proposed method can provide good fault distance estimation accuracy for different ground fault scenarios with variable fault resistance. Compared with the traditional double-circuit line protection method, the proposed method which requires the same equipment investment and offers better performance is more suitable for industry application.Keywords
Funding Information
- National High-tech R&D Program of China (863 Program) (2012AA050208)
- NSFC (51407067, 51222703)
- “111” project (B08013)
This publication has 15 references indexed in Scilit:
- Effects of High Fault Currents on Ground Grid DesignIEEE Transactions on Industry Applications, 2010
- High-Resistance Faults on Two Terminal Parallel Transmission Line: Analysis, Simulation Studies, and an Adaptive Distance Relaying SchemeIEEE Transactions on Power Delivery, 2007
- An adaptive scheme for parallel-line distance protectionIEEE Transactions on Power Delivery, 2002
- Analysis of very-high-resistance grounding in high-voltage longwall power systemsIEEE Transactions on Industry Applications, 2001
- Enhanced double circuit line protectionIEEE Transactions on Power Delivery, 1997
- Adaptive distance protection of double-circuit lines using artificial neural networksIEEE Transactions on Power Delivery, 1997
- Adaptive distance protection of a double-circuit lineIEEE Transactions on Power Delivery, 1994
- Modification in Waveform of Traveling Pulse Voltages Due to Corona Production Along Transmission LineIEEE Transactions on Industry Applications, 1985
- A New Alogorithm of an Accurate Fault Location for EHV/UHV Transmission Lines: Part I - Fourier Transformation MethodIEEE Transactions on Power Apparatus and Systems, 1981
- A Review of Lightning Protection and Grounding PracticesIEEE Transactions on Industry Applications, 1973