The article discusses the feasibility of combining two substations into a single complex or the use of two-transformer substations with unbalanced load curve of the enterprise, when it is beneficial to reduce the number of switched on transformers when the load drops. At the same time, power transformers are equipped with special reactor-thyristor devices for switching them on under load without a surge and asymmetry of inrush currents and voltage dips, switching off without arcing at the contacts of switches and maintaining the voltage of consumers in dynamic and stationary operating modes at a given level. The results of a study on a model in Matlab environment of two substation transformers with a capacity of 1000 kV·A and a voltage of 10 / 0.4 kV are presented.