Dependence of Flashover on Temperature and Aspect Ratio of the Compartment
Author:
- 1 July 2003
- journal article
- other
- Published by SAGE Publications in Journal of Fire Sciences
- Vol. 21 (4) , 267-284
Abstract
A non-linear model of flashover, FLASHOVER A1, has been used to explore the dependence of the critical fire size necessary for the onset of flashover on the aspect ratio of the enclosure. It may be hypothesized that, overall, there is a dependence on aspect ratio. Further, it has been inferred that the critical upper layer temperature necessary for the onset of flashover is not fixed but depends upon the specific case assumed. It is not tenable to assume a single, fixed, temperature as a criterion for flashover, although this has often been done in the past.Keywords
This publication has 16 references indexed in Scilit:
- Dependence of flashover on assumed value of the discharge coefficientFire Safety Journal, 2001
- On the theory of flashover developmentFire Safety Journal, 1995
- A Model of Instability and FlashoverJournal of Applied Fire Science, 1994
- Nonlinear dynamics of flashover in compartment firesFire Safety Journal, 1993
- Limitations of computer modelsFire Safety Journal, 1992
- A Non-Linear Model of FlashoverFire Science and Technology, 1992
- Entrainment in fire plumesFire Safety Journal, 1981
- Flashover and instabilities in fire behaviorCombustion and Flame, 1980
- Fire Induced Gas Flow in an EnclosureCombustion Science and Technology, 1976
- Fire induced flow through an openingCombustion and Flame, 1975