Abstract
The probabilities of failure for cast iron (CI), ductile iron (DI), polyvinyl chloride (PVC), and concrete cylinder (CC) pipes were analyzed to determine the pipe type that failed most consistently at the Honolulu Board of Water Supply (HBWS). In understanding the process of the probability of failure over time, expected failure rates were calculated. A pipe type with a low and consistent probability of pipe failure was preferred for asset management over one that displayed a high and volatile probability of failure. The probability of failure was derived from the failure rate, assuming a Poisson distribution. The data for each pipe type was analyzed and compared by using control charts, operating characteristic (OC) curves, and process capability indexes. The results of the control charts showed that CC pipes were the most stable. According to the OC curves, in which the hypothesis created was that the probability of failure was less than the upper specification limit, CI pipes had the highest pr...