Thermal Rating of Offshore Wind Farm Cables Installed in Ventilated J-Tubes
Open Access
Abstract
The section of submarine cable that is installed in enclosed J-tubes represents a possible thermal limiting point along the export circuits of offshore wind farms (OWFs). To obtain higher continuous thermal ratings for J-tube systems, a ventilated design, realized by allowing for the flow of natural wind into the J-tube through vents, is considered in this paper. To evaluate the performance of this forced-ventilation design, a coupled three-dimensional (3D) numerical model is constructed using the computational fluid dynamics (CFD) technique. The CFD method is first successfully tested through comparisons with existing methods for enclosed J-tubes. Then, the cable rating for the ventilated design is determined using the CFD model and compared with the rating for the enclosed case. The results show that the cooling effect from forced ventilation is obvious, and the cable rating could be increased by up to 27.5% for a wind speed of 10 m/s. This improvement in rating is especially significant for OWFs where the export circuit output is limited by the cable rating in enclosed J-tubes.Keywords
This publication has 12 references indexed in Scilit:
- Analysis of Switching Transients during Energization in Large Offshore Wind FarmsEnergies, 2018
- Investigation of the Ampacity of a Prefabricated Straight-Through Joint of High Voltage CableEnergies, 2017
- Analytical Thermal Rating Method for Cables Installed in J-TubesIEEE Transactions on Power Delivery, 2016
- Trends of offshore wind projectsRenewable and Sustainable Energy Reviews, 2015
- The current state of offshore wind energy technology developmentEnergy, 2012
- The cost of offshore wind: Understanding the past and projecting the futureEnergy Policy, 2012
- Cost Reduction Prospects for Offshore Wind FarmsWind Engineering, 2004
- Rating of cables on riser poles, in trays, in tunnels and shafts-a reviewIEEE Transactions on Power Delivery, 1996
- Experimental Investigation of Free Convection in a Vertical Rod Bundle—A General Correlation for Nusselt NumbersJournal of Heat Transfer, 1985
- Ampacity of Electric Power Cables in Vertical Protective RisersIEEE Transactions on Power Apparatus and Systems, 1983