PERFORMANCE EVALUATION OF VAPOR COMPRESSION REFRIGERATION SYSTEM BY VARYING AIR FLOW RATES IN AIR-COOLED AND EVAPORATIVELY COOLED CONDENSERS

Authors:

Abstract
Increasing the coefficient of performance of vapor compression refrigeration systems with conventional air-cooled condensers is a challenging problem especially in areas having adverse ambient conditions. An effective way of tackling this problem is by employing an evaporative-cooled condenser. In this paper, the effect of evaporative cooling on the performance of the VCRS under three different ambient temperatures of 23°C, 29°C and 35°C is studied. It also compares the effect of using cellulose and steel-wire mesh pads in an evaporative cooler. The effect on the performance of VCRS is also evaluated by varying three different air flow rates i.e (1.15, 0.93 and 0.88 m/s) in air cooled and evaporative cooled condenser. Experimental results show that at 23°C for air flow rate of 0.88 m/s the performance of the system is increased by 2.3% and 1.1 % by employing an evaporative cooler using cellulose and steel-wire pads respectively as compared to air cooled condenser. Effect on the performance of the system will be more pronounced if evaporative coolers having high heat transfer coefficients are employed.