Reducing Legionella Colonization of Water Systems with Monochloramine
Open Access
- 1 April 2006
- journal article
- Published by Centers for Disease Control and Prevention (CDC) in Emerging Infectious Diseases
- Vol. 12 (4) , 588-596
Abstract
Monochloramine disinfection of municipal water supplies is associated with decreased risk for Legionnaires' disease. We conducted a 2-year, prospective, environmental study to evaluate whether converting from chlorine to monochloramine for water disinfection would decrease Legionella colonization of hot water systems. Water and biofilm samples from 53 buildings were collected for Legionella culture during 6 intervals. Prevalence ratios (PRs) comparing Legionella colonization before and after monochloramine disinfection were adjusted for water system characteristics. Legionella colonized 60% of the hot water systems before monochloramine versus 4% after conversion (PR 0.07, 95% confidence interval 0.03–0.16). The median number of colonized sites per building decreased with monochloramine disinfection. Increased prevalence of Legionella colonization was associated with water heater temperatures <50°C, buildings taller than 10 stories, and interruptions in water service. Increasing use of monochloramine in water supplies throughout the United States may reduce Legionella transmission and incidence of Legionnaires' disease.Keywords
This publication has 29 references indexed in Scilit:
- Introduction of Monochloramine into a Municipal Water System: Impact on Colonization of Buildings by Legionella sppApplied and Environmental Microbiology, 2006
- Environmental Cultures and Hospital-Acquired Legionnaires' Disease: A 5-Year Prospective Study in 20 Hospitals in Catalonia, SpainInfection Control & Hospital Epidemiology, 2004
- Decline in Microbial Studies for Patients with Pulmonary InfectionsClinical Infectious Diseases, 2004
- Pan-European Study on Culture-Proven Legionnaires' Disease: Distribution of Legionella pneumophila Serogroups and Monoclonal SubgroupsEuropean Journal of Clinical Microbiology & Infectious Diseases, 2002
- Legionella and Legionnaires' Disease: 25 Years of InvestigationClinical Microbiology Reviews, 2002
- Negative Effect of High pH on Biocidal Efficacy of Copper and Silver Ions in Controlling Legionella pneumophilaApplied and Environmental Microbiology, 2002
- Active Bacterial Core Surveillance of the Emerging Infections Program NetworkEmerging Infectious Diseases, 2001
- Four Years of Experience with Silver-Copper Ionization for Control of Legionella in a German University Hospital Hot Water Plumbing SystemClinical Infectious Diseases, 1999
- Hospital Characteristics Associated With Colonization of Water Systems byLegionellaand Risk of Nosocomial Legionnaires' Disease: A Cohort Study of 15 HospitalsInfection Control & Hospital Epidemiology, 1999
- Inactivation of Legionella pneumophila by monochloramineJournal of Applied Bacteriology, 1990