Circuit Breaker Recovery Voltages Magnitudes and Rates of Rise
Authors:
- 1 March 1931
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in Transactions of the American Institute of Electrical Engineers
- Vol. 50 (1) , 204-238
Abstract
This paper shows the conditions affecting the magnitude and rate of rise of recovery voltage at the terminals of an oil circuit breaker upon interruption of a short circuit, and explains their effect in quantitative terms. Factors are presented whose numerical value takes into account the number of phases involved in the short circuit and the ground connections of short circuit and generator, the decrement of short-circuit current previous to interruption, and the effect of unequal reactances in the direct and quadrature axes of synchronous machines. It is also indicated how to take into account the effect of displacement and of initial load current, and the effect of saturation is discussed very briefly. Magnetic oscillograms are presented which verify the most important of the points brought out. The most common locations and a rough idea of the magnitude of the capacitances affecting the rate of rise of recovery voltage for various types of short circuit are indicated. Calculations of the recovery voltage curve for several representative cases, at both low and high voltages, are presented, and in some cases cathode ray oscillograms are presented for comparison with the calculated curves. While no systematic data appear to be available at present regarding the effect of the rate of recovery voltage rise upon circuit breaker operation, several tests showing a very pronounced effect, some of them made by the authors and some by others, are reported briefly.Keywords
This publication has 12 references indexed in Scilit:
- The Reactances of Synchronous MachinesTransactions of the American Institute of Electrical Engineers, 1928
- Equipment for 220-Kv. SystemsTransactions of the American Institute of Electrical Engineers, 1928
- High-voltage oil circuit breakers for transmission networksJournal of the A.I.E.E., 1927
- Circuit breaker developmentJournal of the A.I.E.E., 1927
- Transmission Line Voltage SurgesTransactions of the American Institute of Electrical Engineers, 1927
- Three-Phase, 60,000-Kv-a. Turbo Alternators for GennevilliersTransactions of the American Institute of Electrical Engineers, 1925
- The Oil Circuit Breaker Situation from an Operator's ViewpointTransactions of the American Institute of Electrical Engineers, 1925
- Oil Circuit Breaker Investigation as Carried on with a 26,700-Kv-a. GeneratorTransactions of the American Institute of Electrical Engineers, 1924
- Circuit Breaker Tests at Bessemer, Ala. On 300-Ampere, 110,000-Volt BreakersTransactions of the American Institute of Electrical Engineers, 1924
- Tests on General Electric Oil Circuit Breakers at BaltimoreTransactions of the American Institute of Electrical Engineers, 1922