Improving Fault Ride-Through Capability of DFIG-Based Wind Turbine Using Superconducting Fault Current Limiter
- 20 December 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Applied Superconductivity
- Vol. 23 (3) , 5601204
Abstract
With increased penetration of wind energy as a renewable energy source, there is a need to keep wind turbines connected to the grid during different disturbances such as grid faults. In this paper, the use of superconducting fault current limiter (SFCL) is proposed to reduce fault current level at the stator side and improve the fault ride-through (FRT) capability of the system. To highlight the proposed technique, a doubly fed induction generator (DFIG) is considered as a wind-turbine generator, where the whole system is simulated using PSCAD/EMTDC software. Detailed simulation results are obtained with and without SFCL considering stator and rotor currents. In addition, the voltage profile at the generator terminals is analyzed. The effect of limiting resistance value is also investigated. The obtained results ensure that the SFCL is effective in decreasing the fault current. Moreover, both the voltage dip at the generator terminals and the reactive power consumption from the grid are decreased during the fault. The voltage dip characteristics are discussed in accordance with international grid codes for wind turbines.Keywords
This publication has 14 references indexed in Scilit:
- Application of SMES to Enhance the Dynamic Performance of DFIG During Voltage Sag and SwellIEEE Transactions on Applied Superconductivity, 2012
- Wind Farms Fault Ride Through Using DFIG With New Protection SchemeIEEE Transactions on Sustainable Energy, 2012
- Current–Time Characteristics of Resistive Superconducting Fault Current LimitersIEEE Transactions on Applied Superconductivity, 2012
- Modeling and Ride-Through Control of Doubly Fed Induction Generators During Symmetrical Voltage SagsIEEE Transactions on Energy Conversion, 2011
- Decoupled-DFIG Fault Ride-Through Strategy for Enhanced Stability Performance During Grid FaultsIEEE Transactions on Sustainable Energy, 2010
- A review of grid code technical requirements for wind farmsIET Renewable Power Generation, 2009
- Providing Ride-Through Capability to a Doubly Fed Induction Generator Under Unbalanced Voltage DipsIEEE Transactions on Power Electronics, 2009
- Thermal and Electrical Analysis of Coated Conductor Under AC Over-CurrentIEEE Transactions on Applied Superconductivity, 2007
- Wind Power Integration: Connection and system operational aspects2007
- Ridethrough of Wind Turbines with Doubly-Fed Induction Generator During a Voltage DipIEEE Transactions on Energy Conversion, 2005