Pollution Flashover Under Different Contamination Profiles on High Voltage Insulator: Numerical and Experiment Investigation
Open Access
- 2 March 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 9, 37800-37812
Abstract
This work aimed to study the influence of contamination profiles and humidity on flashover electrical characteristics of polluted insulators. Firstly, the flashover tests on cap and pin glass insulators under four pollution levels represented by salinity were conducted. Eight artificial contamination profiles based on the solid layer method have been modeled for the selected insulators. The numerical analysis has been used to determine the insulator electrical characteristics such as potential, electric field, and power dissipation under proposed contamination profiles using finite element methods (FEM). Next, the power dissipation has been simulated with consideration of thermal stress propagation in locations with high power. Finally, flashover voltage gradient tests have been conducted under various humidity and contamination profiles. The values of the flashover voltage gradient due to pollution were determined as the percentage of the value of the flashover voltage gradient in the clean condition which was identified as the reference point. The numerical model indicated that the initiation of arc generally occurs at area in which the electric field and power dissipation is maximum. It was also observed from experimental results that the flashover voltage gradient under different contamination profiles has different values depends on the location and dimension of the pollution region.Keywords
Funding Information
- Ministry of Higher Education (MOHE) through the Fundamental Research Grant Scheme (K301)
- University Tun Hussein Onn Malaysia
- Collaborative Research in Engineering, Science, and Technology (304/PELECT/6050423/C121)
This publication has 30 references indexed in Scilit:
- Contamination effects on charge distribution measurement of high voltage glass insulator stringMeasurement, 2017
- Numerical Computation of Electric Field and Potential Along Silicone Rubber Insulators Under Contaminated and Dry Band Conditions3D Research, 2016
- Electrical field computation of polymeric insulator using reduced dimension modelingIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- DC flashover performance of insulator string with fan-shaped non-uniform pollutionIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Risk assessment of desert pollution on composite high voltage insulatorsJournal of Advanced Research, 2014
- Study on AC Flashover Performance for Different Types of Porcelain and Glass Insulators With Non-Uniform PollutionIEEE Transactions on Power Delivery, 2013
- Simulation and measurement of the voltage distribution on high voltage suspension Porcelain insulator string under pollution conditionInternational Journal of Applied Science and Engineering Research, 2012
- Effect of non-uniform pollution on the withstand characteristics of extra high voltage (EHV) suspension ceramic insulator stringIET Generation, Transmission & Distribution, 2010
- Initiation of dry bands on polluted insulationProceedings of the Institution of Electrical Engineers, 1968
- Flashover mechanism of polluted insulationProceedings of the Institution of Electrical Engineers, 1964