Analysis of very fast transients in transformers
Authors:
- 1 January 2001
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Generation, Transmission and Distribution
- Vol. 148 (5) , 377-383
Abstract
Very fast transient overvoltages generated in gas-insulated switchgear could cause a voltage oscillation inside the connected transformer. A practical method to calculate the high- frequency transients in the transformer winding is developed based on multiconductor transmission-line theory. Resonance characteristics of a transformer are assessed using the inductance matrix obtainable from its winding geometry. Applicability to transients of frequencies up to several megahertz is checked in a model transformer and an actual 500 kV transformer. The calculated interturn voltage waveforms are in particularly good agreement with experiment.Keywords
This publication has 8 references indexed in Scilit:
- Voltage Oscillation in Transformer Windings Affected by Very Fast Transient SurgesIEEJ Transactions on Power and Energy, 2000
- Effects of very fast transient overvoltages on transformerIEE Proceedings - Generation, Transmission and Distribution, 1999
- Experimental investigation of high frequency voltage oscillation in transformer windingsIEEE Transactions on Power Delivery, 1998
- Analysis of very fast transient overvoltage in transformer windingIEE Proceedings - Generation, Transmission and Distribution, 1997
- A method for constructing reduced order transformer models for system studies from detailed lumped parameter modelsIEEE Transactions on Power Delivery, 1992
- A computer model for calculating steep-fronted surge distribution in machine windingsIEEE Transactions on Energy Conversion, 1989
- A Calculation Method for Impulse Voltage Distribution and Transferred Voltage in Transformer WindingsIEEE Transactions on Power Apparatus and Systems, 1978
- Transient Oscillations in Multiwinding TransformersIEEE Transactions on Power Apparatus and Systems, 1974