Variable Extinction Angle Control Strategy Based on Virtual Resistance to Mitigate Commutation Failures in HVDC System
Open Access
- 12 May 2020
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 8, 93692-93704
Abstract
To mitigate commutation failures (CFs) and minimize the instability of HVDC systems due to AC faults or control mode ambiguity, a constant extinction voltage-time area based control strategy with virtual resistance is proposed. In this strategy, using sine-cosine components detector and considering zero-crossing phase shift of commutation voltage, the extinction angle setting value can be adjusted dynamically. Meanwhile, to reflect the characteristics of DC current during the fault and recovery process, a virtual resistance is introduced into the control system and DC voltage considering the voltage drop of the virtual resistance is taken as the input of voltage-dependent current order limiter (VDCOL). Through theoretical analysis, the proposed strategy not only reduces the firing angle dynamically, but also reduces DC current by lowering the current order on the rectifier side immediately when the AC voltage disturbance is detected, thereby further reducing the occurrence of CFs. Therefore, the control strategy can effectively suppress successive and intermittent CFs. The effectiveness of the proposed control strategy is verified by simulation of the single HVDC and multi-infeed HVDC model based on the CIGRE HVDC benchmark system, in which AC-DC current criterion of identifying CF and suppression ratio index are adopted. The simulation results show that the proposed control strategy can effectively mitigate CFs under single-phase and three-phase faults to a certain extent. Comparing with the existing control strategies based on controller modification, i.e. commutation failure prevention, DC current predictive control, smooth logic switching control and DC current limitation control strategy based on virtual resistance, the proposed control strategy is superior in mitigation effects. The average suppression rates of these strategies are 1.66%, 3.21%, 6.11%, 3.35%, and 8.33% under single-phase fault, respectively; with the rates of 1.4%, 2.72%, 4.97%, 0%, and 6.8% under three-phase fault, respectively.Keywords
Funding Information
- National Natural Science Foundation of China (51507126)
This publication has 35 references indexed in Scilit:
- Power Component Fault Detection Method and Improved Current Order Limiter Control for Commutation Failure Mitigation in HVDCIEEE Transactions on Power Delivery, 2015
- Fast Calculation of Power Oscillation Peak Value on AC Tie-Line After HVDC Commutation FailureIEEE Transactions on Power Systems, 2014
- Direct-Current Predictive Control Strategy for Inhibiting Commutation Failure in HVDC ConverterIEEE Transactions on Power Systems, 2014
- Design of self-tuning controllers for a two terminal HVDC linkInternational Journal of Electrical Power & Energy Systems, 2009
- Hybrid HVDC System for Power Transmission to Island NetworksIEEE Transactions on Power Delivery, 2004
- Decreasing the commutation failure frequency in HVDC transmission systemsIEEE Transactions on Power Delivery, 2000
- Capacitor commutated converter circuit configurations for DC transmissionIEEE Transactions on Power Delivery, 1998
- Fast and predictive HVDC extinction angle controlIEEE Transactions on Power Systems, 1997
- Commutation failures in HVDC transmission systemsIEEE Transactions on Power Delivery, 1996
- Dynamic performance of static and synchronous compensators at an HVDC inverter bus in a very weak AC systemIEEE Transactions on Power Systems, 1994