Characterization, calibration and macromodeling of RF current probes
Authors:
- 1 December 2009
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 21654727,p. 629-632
Abstract
Characterization of a current probe by measuring three port S-parameters with the probe clamped to a calibration fixture is presented. A simple calibration fixture based on a wire over ground plane is used. From the measured 3-port S-parameters, accurate de-embedding is performed to remove the fixture and transmission line effects to obtain the S-parameters of the current probe. Equivalent circuit representation of the fixture is utilized in the de-embedding procedure. Subsequently, vector fitting based macromodeling of the de-embedded S-parameters of the probe is performed. SPICE-compatible equivalent circuits are then obtained and their use in the simulation of physical tests with circuit simulators is demonstrated. Results for both commercial and simple in-house designed current probes are presented.Keywords
This publication has 6 references indexed in Scilit:
- Circuit Modeling of Injection Probes for Bulk Current InjectionIEEE Transactions on Electromagnetic Compatibility, 2007
- Wide-band characterization of current probesIEEE Transactions on Electromagnetic Compatibility, 2003
- Synthesis of SPICE-compatible broadband electrical models from n-port scattering parameter data2003
- Enforcing passivity for admittance matrices approximated by rational functionsIEEE Transactions on Power Systems, 2001
- Rational approximation of frequency domain responses by vector fittingIEEE Transactions on Power Delivery, 1999
- Inductance Calculations in a Complex Integrated Circuit EnvironmentIBM Journal of Research and Development, 1972