SPLL design to flux oriented of a VSC interface for wind power applications
Authors:
- 1 January 2005
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 6 pp.
Abstract
Accurate phase information is crucial for most of modern power electronic systems such as VSC connected to the grid. In this paper, it is proposed an algorithm software phase-locked loop (SPLL) to obtain phase and frequency information of the grid voltage. This is based in an algorithm of on-line separation of the grid voltage sequences (DSC), and a discrete traditional PLL. A criterion to tune the SPLL constants from a PLL discrete linearized model is discussed. The SPLL response is evaluated for different grid disturbances and different SPLL parameters. Besides, a VSC connected to the grid through and L filter with the SPLL obtained in this paper has been tested for different configurations of SPLL and different grid perturbations. Conclusions about where to apply the SPLL different configurations are obtained from these last tests.Keywords
This publication has 4 references indexed in Scilit:
- Transient operation of grid-connected voltage source converter under unbalanced voltage conditions2002
- Phase-locked loop for grid-connectedthree-phase power conversion systemsIEE Proceedings - Electric Power Applications, 2000
- Shunt active filtering of vector current-controlled VSC at a moderate switching frequencyIEEE Transactions on Industry Applications, 1999
- Operation of a phase locked loop system under distorted utility conditionsIEEE Transactions on Industry Applications, 1997