UHF couplers for gas-insulated substations:a calibration technique
Authors:
- 8 May 1997
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Science, Measurement and Technology
- Vol. 144 (3) , 117-122
Abstract
Methods that have been used to evaluate the performance of UHF couplers for partial discharge monitoring of gas-insulated substations are briefly reviewed, illustrating the need for a standard test procedure. A measurement scheme is proposed in which the coupler is mounted beneath an aperture in a ground plane and subjected to an incident electric field of known intensity. A TEM line is used to evaluate the technique, and a step excitation is shown to have advantages over swept frequency measurements. The frequency responses of two disc couplers and an external window coupler are measured to demonstrate the technique.Keywords
This publication has 5 references indexed in Scilit:
- The excitation of UHF signals by partial discharges in GISIEEE Transactions on Dielectrics and Electrical Insulation, 1996
- Modelling partial discharge excitationof UHF signals in waveguidestructures using Green's functionsIEE Proceedings - Science, Measurement and Technology, 1996
- Broadband couplers for UHF detection of partial discharge in gas-insulated substationsIEE Proceedings - Science, Measurement and Technology, 1995
- Calibration of RF field strength metersIEEE Transactions on Instrumentation and Measurement, 1995
- Partial discharge diagnostics for gas insulated substationsIEEE Transactions on Dielectrics and Electrical Insulation, 1995