Lead leaching from inline brass devices: A critical evaluation of the existing standard
Authors:
- Abhijeet DudiADAbhijeet Dudi
- Michael SchockMSMichael Schock
- Nestor MurrayNMNestor Murray
- Marc EdwardsMEMarc Edwards
- 1 August 2005
- journal article
- research article
- Published by Wiley in Journal AWWA
- Vol. 97 (8) , 66-78
Abstract
The American National Standards Institute/NSF Standard 61, Section 8, is intended to protect the public from inline brass plumbing products that might leach excessive levels of lead to potable water. Experiments were conducted to examine the practical rigor of this test. Contrary to expectations, the test was not highly protective of public health. In fact, results indicated that small devices made of pure lead—which pose an obvious public hazard—can easily pass the leaching protocol. Reforms are needed to help prevent such unacceptable outcomes in the future. Brass devices passing the test can contribute to lead levels at the tap in residences, schools, and other buildings.Keywords
Funding Information
- National Science Foundation (DMI‐0329474)
This publication has 13 references indexed in Scilit:
- Phosphate inhibitor use at US utilitiesJournal AWWA, 2002
- Phosphate inhibition of soluble copper corrosion by-product releaseCorrosion Science, 2002
- Effect of PHOSPHATE inhibitors on lead release from pipesJournal AWWA, 2002
- Desktop guidance for mitigating Pb and Cu corrosion by‐productsJournal AWWA, 1999
- Using aeration for corrosion controlJournal AWWA, 1998
- Alkalinity, pH, and copper corrosion by‐product releaseJournal AWWA, 1996
- Corrosion control on the basis of utility experienceJournal AWWA, 1995
- A Laboratory Study of the Leaching of Lead From Water FaucetsJournal AWWA, 1989
- Understanding Corrosion Control Strategies for LeadJournal AWWA, 1989
- The drinking-water additives programEnvironmental Science & Technology, 1989