Vacuum Circuit Breaker Transients During Switching of an LMF Transformer
Authors:
- 9 November 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 48 (1) , 37-44
Abstract
Switching transients associated with circuit breakers have been observed for many years. With the widespread application of vacuum breakers for transformer switching, recently, this phenomenon has been attributed to a significant number of transformer failures. Vacuum circuit breaker switching of electric arc furnace and ladle melt furnace (LMF) transformers raises concern because of their inductive currents. High-frequency transients and overvoltages result when the vacuum breaker exhibits virtual current chop and multiple re-ignitions. This paper will present a detailed case study of vacuum breaker switching of a new LMF transformer involving current chopping and restrike simulations using the electromagnetic transients program. A technique that involves a combination of surge arresters and snubbers will be applied to the LMF to show that the switching transients can be successfully mitigated. Additionally, some practical aspects of the physical design and installation of the snubber will be discussed.Keywords
This publication has 3 references indexed in Scilit:
- Transformer failure due to circuit breaker induced switching transients2010
- Characteristics and applications of various arc interrupting methodsIEEE Transactions on Industry Applications, 1991
- Extensive field measurements support new approach to protection of arc furnace transformers against switching transientsIEEE Transactions on Power Apparatus and Systems, 1975