A new principle of discrimination between inrush current and internal fault current of transformer based on self-correction function
Authors:
- 1 January 2005
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 19471262,p. 614-617 Vol. 2
Abstract
When differential protective relays are applied to transformer protection, how to identify the magnetizing inrush current and short circuit current caused by internal fault is the key problem. Here, regarding the inrush current and short circuit current as the random signal, the sampled data are analyzed by correlation function principle in the digital signal processing (DSP) and the self-correlation function of the sampled data is calculated. Through the similar comparison operation conducted by standard self-correlation function (SSCF) formed with sinusoidal current the short circuit current and the inrush current can be distinguished by the magnitude of similarity coefficient. The results in electrical power dynamic laboratory (EPDL) verify the feasibility of the proposed methodKeywords
This publication has 5 references indexed in Scilit:
- A wavelet-based technique for discrimination between faults and magnetizing inrush currents in transformersIEEE Transactions on Power Delivery, 2003
- Studies for identification of the inrush based on improved correlation algorithmIEEE Transactions on Power Delivery, 2002
- Experimental testing of the artificial neural network based protection of power transformersIEEE Transactions on Power Delivery, 1998
- Digital relays improve protection of large transformersIEEE Computer Applications in Power, 1998
- A state-of-the-art review of transformer protection algorithmsIEEE Transactions on Power Delivery, 1988