Comparison and Evaluation of Induction Generator Models in Wind Turbine Systems for Transient Stability of Power System
Authors:
- 1 October 2006
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Abstract
In order to analyze the transient stability of grid-connected squirrel cage induction generators (SCIG) in wind power generating systems, various mathematical models, including the detailed and reduced generator models as well as the one-mass and two-mass shaft system models, are studied in this paper. Based on the different wind turbine system models, the dynamic behaviors are simulated and compared by using Matlab/Simulink, under the condition that the generator stator terminal is subjected to a three-phase short-circuit fault. In addition, the critical clearing time (CCT) is calculated and compared by using a direct method with critical clearing slip of induction generators and a method of trial and error by simulation, for different system models at the various operation conditions. The models and methods suitable to analyze the transient stability of the wind turbine systems based on SCIG are discussed in detail. Several comparative results have shown that the valid transient stability model of SCIG in wind turbine systems has to incorporate the two-mass shaft system model, the direct method of CCT estimation based on critical clearing slip is incompatible to determine the transient stability limit, owing to the large multi-oscillation of the generator rotor speed during the fault period.Keywords
This publication has 10 references indexed in Scilit:
- Issues of Connecting Wind Farms into Power Systems2005
- Wind generation dynamic simulation connected to an electric power system2005
- On Speed StabilityIEEE Transactions on Power Systems, 2005
- Investigation of Induction Machine Contribution to Power System OscillationsIEEE Transactions on Power Systems, 2005
- System Impact Study for the Interconnection of Wind Generation and Utility SystemIEEE Transactions on Industry Applications, 2005
- Fixed-Speed Wind-Generator and Wind-Park Modeling for Transient Stability StudiesIEEE Transactions on Power Systems, 2004
- Fixed-speed active-stall wind turbines in offshore applicationsEuropean Transactions on Electrical Power, 2004
- Definition and Classification of Power System Stability IEEE/CIGRE Joint Task Force on Stability Terms and DefinitionsIEEE Transactions on Power Systems, 2004
- Investigation into the estimation of the critical clearing time of a grid connected wind power based embedded generator2003
- Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbancesIEE Proceedings - Generation, Transmission and Distribution, 2003