Impact of icing severity on corona performance of glaze ice-covered conductor
Authors:
- 27 November 2017
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 24 (5) , 2952-2959
Abstract
This paper presents the results of laboratory experiments carried out on an ac-energized stranded conductor subjected to simulated glaze icing, which were conducted in a corona cage located in an artificial climate chamber. With the increase of icing duration, the grow of icing severity of conductors lead to the corona onset voltage fell from 54.8 to 41.9 kV, correspondingly, the surface irregularity of stranded conductor decreased from 0.41 to 0.31. Through the ultraviolet photon frame and ultraviolet photon curve, corona development process of glaze ice-covered conductor were divided into three stages, that is, burst corona mode, comprehensive corona mode and glow mode. The impact of icing severity on the corona loss and audible noise was investigated. With regard to corona loss, it is in proportion to icing severity at a given surface gradient, whereas no obvious impact was observed with audible noise could be established. In addition, corona performance in comparison with rain condition was also studied, the corona loss of glaze ice-covered conductor was higher than that of rain, instead the audible noise of glaze ice-covered conductor was lower than that of rain after a certain surface gradient. The presented results could provide references to the design of ac overhead transmission lines crossing cold regions.Keywords
This publication has 20 references indexed in Scilit:
- Analysis of Ice-Covering Characteristics of China Hunan Power GridIEEE Transactions on Industry Applications, 2014
- Study on the influence of charged glaze on the corona onset voltage of bundle conductorIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Calculating the Surface Potential Gradient of Overhead Line ConductorsIEEE Transactions on Power Delivery, 2014
- Historical analogues of the 2008 extreme snow event over Central and Southern ChinaClimate Research, 2011
- Mechanism of the tonal emission from ac high voltage overhead transmission linesJournal of Physics D: Applied Physics, 2011
- Onset voltage of negative corona on stranded conductorsJournal of Physics D: Applied Physics, 2007
- Corona loss characteristics of contaminated conductors in fair weatherElectric Power Systems Research, 2001
- Ice accretions on high–voltage conductors and insulators and related phenomenaPhilosophical Transactions of the Royal Society A: Mathematical, Physical and Engineering Sciences, 2000
- Transmission line corona losses under hoar frost conditionsIEEE Transactions on Power Delivery, 1997
- Corona from Ice PointsJournal of Applied Physics, 1951