Method to determine the power efficiency of UV disinfection plants and its application to low pressure plants for drinking water
- 5 December 2016
- journal article
- Published by IWA Publishing in Water Supply
- Vol. 17 (4) , 947-957
Abstract
In this paper we present a method to determine the power efficiency of ultraviolet (UV) disinfection plants and apply this to low pressure plants for drinking water. In UV disinfection plants the water flow is regulated to ensure that micro-organisms receive the necessary fluence for inactivation while passing through. The flow depends on the UV transmission (UVT) of the water. As lower the UVT of the water is, the less water may flow through the plant. UV irradiance is produced by lamps that consume, together with other components, electrical power and entail running costs. The power efficiency – electrical power versus disinfected volume – of a plant has therefore an important impact. Applying this method to different UV plants, which are on the market, shows that at least an electric power of 5.3 Wh is necessary to disinfect 1 m3 of water possessing a UVT of 80% (100 mm), 8 Wh at 50% and 22 Wh at 10%. Further we found that ineffective design or a wrong selection of a plant may enhance these values by a factor up to 7. This method enables not only to calculate the power efficiency but also to decide for a certain plant type.Keywords
This publication has 11 references indexed in Scilit:
- Ten-year monitoring of an ultraviolet disinfection plant for drinking waterJournal of Environmental Engineering and Science, 2015
- Aging of low-pressure amalgam lamps and UV dose deliveryJournal of Environmental Engineering and Science, 2014
- Effect of a protective layer on the lifetime and output radiation intensity decay rate of quartz low-pressure gas discharge lampsTechnical Physics Letters, 2006
- Amalgams for fluorescent lampsJournal of Alloys and Compounds, 2000
- Amalgams for fluorescent lamps: Part I: Thermodynamic design rules and limitationsJournal of Alloys and Compounds, 2000
- Effect of UV System Modifications on Disinfection PerformanceJournal of Environmental Engineering, 1999
- Integrated UV Disinfection Model Based on Particle TrackingJournal of Environmental Engineering, 1999
- Biodosimetry: Model calculations for u.v. water disinfection devices with regard to dose distributionsWater Research, 1996
- Some New Mercury Alloys for Use in Fluorescent LampsJournal of the Illuminating Engineering Society, 1977
- Die Aktivitätskoeffizienten des Hg im Indiumamalgam beim Übergang von der festen zur flüssigen Phase / The activity coefficients of hg in in-amalgams at the solid-liquid phase transitionZeitschrift für Naturforschung A, 1971