Abstract
The progressive replacement of synchronous generation by inverter-based resources is significantly reducing the inertia of modern power systems, introducing new frequency stability challenges under severe disturbances. This work analyses how the key characteristics of Fast Frequency Response (FFR) services provided by Battery Energy Storage Systems (BESS) -- specifically response time and control design -- influence frequency dynamics and modify the FFR reserve required for secure operation in the Iberian Peninsula.The power system is represented through a detailed large-scale transmission network model. The results highlight the importance of detailed nodal transient simulations for accurately assessing the dynamic behaviour of future low-inertia grids. Additionally, the work establishes operational maps defining different stability regions for Iberian Peninsula-Continental Europe disconnection scenarios, providing insights into the relationship between FFR characteristics, reserve requirements, and secure operating conditions.