Abstract
Inter-area oscillation is a major problem of modern interconnected power system (ICPS). It can be eliminated using wide-area damping controller (WADC). It is well known that wide-area signal is very effective as feedback signal of the WADC, to mitigate the inter-area oscillation of an interconnected power system. Wide-area measurement systems (WAMS) is very useful to collect the wide-area signal but, communication delay and communication failure can occur at any time in WAMS using communication channels and can deteriorate the effectiveness of the WADC. A WADC, which is resilient to communication failure, is demonstrated in this work contemplating transmission latency in the communication network and saturation of the actuator. The control action is developed using state feedback action and a linear matrix inequality (LMI) based condition is derived as the necessary condition to achieve stability of the power system. A supplementary damping controller (SDC) is used as the controller of a thyristor controlled series capacitor (TCSC). The role of the actuator and WADC is taken by TCSC and SDC respectively. The control algorithm ensures that the SDC supplies sufficient damping to enhance the small signal stability of the power system. The efficacy of the developed control algorithm is tested using a 11-bus system and a IEEE 39-bus power system.