Evaluating harmonic voltage distortion in load‐variating unbalanced networks using Monte Carlo simulations
Open Access
- 1 June 2015
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 9 (9) , 855-865
Abstract
This study presents a new methodology for modelling and handling with aggregated harmonic loads and linear loads in the harmonic power flow analysis. This method, so‐called variable load method, can be used in balanced and unbalanced systems and for deterministic and stochastic studies. The main types of harmonic loads and their participation coefficients inside the facility are estimated by inspection or based on usual values. In addition, a new type of load model that represents the load variation and minor loads is also defined based on field measurements, in order to build a more adherent harmonic load representation. A stochastic analysis, based on Monte Carlo simulations, is also performed. This sequence of steps makes possible to evaluate if the harmonic distortion has a significant probability of exceeding the limits set by standards because of load variations. This analysis is performed jointly with the bootstrapping method for obtaining the probability density functions of the voltage harmonic distortions. Tests on a real plant show that the proposed approach is able to represent measured data with high precision.Keywords
Funding Information
- Fundação de Amparo à Pesquisa do Estado de Minas Gerais
- Coordenação de Aperfeiçoamento de Pessoal de Nível Superior
- Conselho Nacional de Desenvolvimento Científico e Tecnológico
This publication has 23 references indexed in Scilit:
- Cancellation and attenuation of harmonics in low voltage networks2014
- Harmonic Analysis in Frequency and Time DomainIEEE Transactions on Power Delivery, 2013
- Assessing the Collective Harmonic Impact of Modern Residential Loads—Part I: MethodologyIEEE Transactions on Power Delivery, 2012
- Harmonic Summation and Assessment Based on Probability DistributionIEEE Transactions on Power Delivery, 2012
- Analyzing systems with distributed harmonic sources including the attenuation and diversity effectsIEEE Transactions on Power Delivery, 2005
- Time-varying harmonics. I. Characterizing measured dataIEEE Transactions on Power Delivery, 1998
- A new frequency domain arc furnace model for iterative harmonic analysisIEEE Transactions on Power Delivery, 1997
- An investigation of harmonics attenuation and diversity among distributed single-phase power electronic loadsIEEE Transactions on Power Delivery, 1995
- Nonparametric estimates of standard error: The jackknife, the bootstrap and other methodsBiometrika, 1981
- Bootstrap Methods: Another Look at the JackknifeThe Annals of Statistics, 1979