On-line PD detection and localization in cross-bonded HV cable systems
Authors:
- 23 October 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 21 (5) , 2217-2224
Abstract
This paper addresses the detection and localization of partial discharge (PD) in crossbonded (CB) high voltage (HV) cables. A great deal has been published in recent years on PD based cable insulation condition monitoring, diagnostics and localization in medium voltage (MV) and high voltage (HV) cables. The topic of pulse propagation and PD source localization in CB HV cable systems has yet to be significantly investigated. The main challenge to PD monitoring of CB HV cables is as a result of the interconnectedness of the sheaths of the three single phase cables. The cross-bonding of the sheaths makes it difficult to localize which of the three phases a PD signal has emanated from. Co-axial cables are used to connect cable sheaths to cable link boxes, for ease of installation and protection against moisture. A second challenge is, therefore, the coupling effect when a PD pulse propagates in HV cable joints and the co-axial cables, making PD detection and localization more complex. The paper presents experimental investigations into PD pulse coupling between the cable center conductor and the sheath and the behavior of PD pulse propagation in CB HV cables. It proposes a model to describe PD pulse propagation in a CB HV cable system to allow monitoring and localization, and also presents the knowledge rules required for PD localization in CB HV cable systems.Keywords
This publication has 8 references indexed in Scilit:
- A novel method to locate PD in polymeric cable systems based on amplitude-frequency (AF) mapIEEE Transactions on Dielectrics and Electrical Insulation, 2007
- A novel technique for partial discharge and breakdown investigation based on current pulse waveform analysisIEEE Transactions on Dielectrics and Electrical Insulation, 2005
- Extraction of high frequency power cable characteristics from S-parameter measurementsIEEE Transactions on Dielectrics and Electrical Insulation, 2004
- Classification of PD patterns in XLPE cables under various soil conditions using statistical technique2003
- Calibration for time domain propagation constant measurements on power cablesIEEE Transactions on Instrumentation and Measurement, 2003
- Fundamentals of partial discharge in the context of field cable testingIEEE Electrical Insulation Magazine, 2000
- New partial discharge detection method for live UHV/EHV cable jointsIEEE Transactions on Electrical Insulation, 1992
- Location and characterization of partial discharge sites in shielded power cablesIEEE Transactions on Power Delivery, 1990