Abstract
Displacement ventilation (DV) produces a vertically non-uniform thermal field, so a fully mixed room representation can conceal the mechanisms that determine occupied-zone temperatures and exhaust heat removal. This paper develops a reduced-order, multi-node vertical thermodynamic model for DV under variable total and spatially distributed sensible loads. The room is represented by conservative horizontal control volumes with explicit air thermal storage, inlet advection, inter-node transport, internal heat gains, envelope exchange, and exhaust removal. A load-resolved thermodynamic heat-removal fraction is derived from the source-attribution form of the energy balance as a complementary diagnostic metric alongside established heat-removal indicators. The numerical implementation uses NumPy, SciPy, and Matplotlib; a stiff BDF integration scheme is used for the coupled transient balances. A node-resolution procedure, energy-balance checks, limiting-case tests, transient load sequences, quasi-steady scenarios, and a controlled comparison with a fully mixed reference are specified. The numerical investigation was conducted across parameterized scenarios representing characteristic thermal and load regimes. The literature synthesis establishes the relevance of three-node and zonal DV models and frames the proposed architecture as a reproducible framework for evaluating vertical load distribution in thermodynamic assessment. The study outlines key thermodynamic criteria for evaluating stratified air-distribution systems.