Evaluation of the UHF method based on the investigation of a partial discharge case in post insulators
Authors:
- 1 December 2017
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 24 (6) , 3669-3676
Abstract
The ultra-high frequency (UHF) method is treated as an effective means for partial discharge (PD) detection in field monitoring in smart substations due to its outstanding noise rejection capacity and satisfying sensitivity to typical insulation defects. However, abundant evidence is still lacked to prove its universality. In this paper, the PD test of an actually manufactured post insulator with potential defects is carried out using several kinds of PD detection methods. Nevertheless, the UHF signal is not able to be detected with the coupler, while PD current pulses with large magnitude are already observed within the coupling device connected to the test object. The balanced measuring system is used to verify the origin of the detected pulses, and the limitation of the UHF method on detecting PD of this type is proved. Attempt are made to locate the defect on the test object by measuring the distribution of the temperature on the surface of the insulator. All the results and data analysis show the specific characteristics of the defect compared with those well investigated before, and demonstrates its value to be further researched in the future.Keywords
This publication has 17 references indexed in Scilit:
- Smart Transformer for Smart Grid—Intelligent Framework and Techniques for Power Transformer Asset ManagementIEEE Transactions on Smart Grid, 2015
- New aspects of UHF PD diagnostics on gas-insulated systemsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Partial discharge initiated by free moving metallic particles on GIS insulator surface: severity diagnosis and assessmentIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Continuous Monitoring of Smart Grid Devices Through Multi Protocol Label SwitchingIEEE Transactions on Smart Grid, 2014
- Analysis of the intrinsic characteristics of the partial discharge induced by typical defects in GISIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Multi-source separation method for partial discharge detection in substations2012
- Partial discharge measurement in the ultra high frequency (UHF) rangeIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- A physical model, describing the nature of partial discharge pulse sequences2002
- Pulse Sequence Analysis - a diagnostic tool based on the physics behind partial dischargesJournal of Physics D: Applied Physics, 2001
- Pulse-sequence analysis: a new method for investigating the physics of PD-induced ageingIEE Proceedings - Science, Measurement and Technology, 1995