Fast Detection of Current Transformer Saturation Using Stacked Denoising Autoencoders
Open Access
Abstract
Malfunctions in relay protection devices are predominantly caused by current transformer (CT) saturation which produces distortion in current measurements and disturbances in power system protection. The development of deep learning in power system protection is on the rise recently because of its robustness. This study presents a CT saturation detection where the secondary current becomes distorted. The proposed scheme offers a wide range of saturation detection and consists of a moving-window technique and stacked denoising autoencoders. Moreover, Bayesian optimization was used to minimize the difficulty of determining neural network structure for the proposed approach. The performance of the algorithm was evaluated for a-g faults on 154 kV and 345 kV overhead transmission line in South Korea. The waveform variation has been generated by PSCAD for different scenarios that heavily influence CT saturation. Moreover, a comparative analysis with other methods demonstrated the superiority of the proposed DNN method. With the proposed algorithm to detect CT saturation, it significantly yielded high accuracy and precision for CT saturation detection which were approximately 99.71% and 99.32%, respectively.Keywords
Funding Information
- Ministry of Education (NRF-2021R1F1A1061798)
This publication has 24 references indexed in Scilit:
- A New Method of Current-Transformer Saturation Detection in the Presence of NoiseIEEE Transactions on Power Delivery, 2014
- Current Transformer Saturation Detection Using Gaussian Mixture ModelsJournal of Applied Research and Technology, 2013
- Detection and correction of distorted current transformer current using wavelet transform and artificial intelligenceIET Generation, Transmission & Distribution, 2008
- A Fast Learning Algorithm for Deep Belief NetsNeural Computation, 2006
- A CT Saturation Detection Algorithm Using Symmetrical Components for Current Differential ProtectionIEEE Transactions on Power Delivery, 2005
- Compensation of the Distortion in the Secondary Current Caused by Saturation and Remanence in a CTIEEE Transactions on Power Delivery, 2004
- A CT saturation detection algorithmIEEE Transactions on Power Delivery, 2004
- Decision trees and wavelet analysis for power transformer protectionIEEE Transactions on Power Delivery, 2002
- An impedance-based CT saturation detection algorithm for busbar differential protectionIEEE Transactions on Power Delivery, 2001
- Improved simulation models for current and voltage transformers in relay studiesIEEE Transactions on Power Delivery, 1992