Abstract
In this research work, a deep learning (DL) based method for the fast and accurate analysis of current harmonics of Electric Arc Furnaces (EAF) is proposed. For such a system, a large amount of EAF current data is required for the training phase of the DL-based structure, which is not only a thorny but also an expensive procedure. Hence, the second focus of this research work is to gain the ability to generate EAF currents with realistic harmonic contents based on a much smaller amount of field data of EAF currents recorded during a tap-to-tap time of the EAF. For this purpose, examination of the EAF current harmonics is achieved on the field data collected at a transformer substation supplying an EAF plant. Then, a significantly larger amount of EAF current data is regenerated mimicking the real EAF behavior to train the DL-based harmonic estimator. This estimator is able to estimate both amplitudes and phases of the harmonics without computing any time- or frequency-domain features during the estimation process. Hence the outcomes of this research work are two-fold: First, detailed analysis of the EAF current harmonic behavior is achieved. Second, a DL-based harmonic estimator is trained, which is able to output amplitude and phase estimations directly out of waveform samples without any feature extraction. The proposed system aims to serve the needs of active power filters of the EAF installations in the electricity system, since it has been shown that fast and accurate harmonic amplitude and phase estimations are obtained.

This publication has 25 references indexed in Scilit: