Influence of protrusions on the positive switching impulse breakdown voltage of sphere‐plane air gaps in high‐altitude areas
Open Access
- 1 June 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Science, Measurement & Technology
- Vol. 14 (4) , 499-504
Abstract
The construction of ultra‐high‐voltage direct‐current power transmission projects in high‐altitude areas calls for the research into the discharge characteristics of the air gaps in the valve hall of a power converter station in such areas. Tests on the switching impulse discharge characteristics of the sphere‐plane air gap were conducted at Yangbajing test base (Tibet, China) at an altitude of 4300 m on conditions that there were burrs on the 1.3 m diameter shield balls. The discharge characteristics, under the influences of burrs with different lengths and locations, were obtained and compared with test data from low‐altitude areas. The results indicate that the arrangements of burrs with different lengths and locations can significantly reduce the switching impulse discharge voltage of sphere‐plane air gaps, while the voltage sag gradually decreased down with increasing burr length. Moreover, the larger the sphere‐plane air gap is, the smaller the influence of such burrs have. High altitude also substantially decreased the switching impulse discharge voltage of the air gap. When the surface of shield balls was smooth, the U50 saturation of the air gap was more significant than at low altitude; however, if there were burrs on the shield balls, the saturation effect was less significant.Keywords
Funding Information
- National Basic Research Program of China (2016YFB0900802)
This publication has 11 references indexed in Scilit:
- The dynamic expansion of leader discharge channels under positive voltage impulse with different rise times in long air gap: Experimental observation and simulation resultsJournal of Applied Physics, 2019
- Influences of surface tips of a shield ball on the discharge characteristics of a long sphere‐plane air gap under positive switching impulsesIET Science, Measurement & Technology, 2018
- Electric Field Distribution and Switching Impulse Discharge under Shield Ball Surface Scratch Defect in an UHVDC HallEnergies, 2018
- Breakdown characteristics of long air gap with negative polarity switching impulseIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- High voltage circuits for applicationof composite voltages to test gapsIEE Proceedings - Science, Measurement and Technology, 1999
- Air density influence on the strength of external insulation under positive impulses: experimental investigation up to an altitude of 3000 m a.s.lIEEE Transactions on Power Delivery, 1990
- Influence of Air Density on the Impulse Strength of External InsulationIEEE Transactions on Power Apparatus and Systems, 1985
- Testing and Commissioning of a Modular UHV AC Outdoor Test SystemIEEE Transactions on Power Apparatus and Systems, 1984
- Switching-surge flashover characteristics of long sphere-plane gaps for UHV station designIEEE Transactions on Power Apparatus and Systems, 1975
- Flashover Tests on Large Air Gaps with DC Voltage and with Switching Surges Superimposed on DC VoltageIEEE Transactions on Power Apparatus and Systems, 1970