PD pattern analysis during induced test of large power transformers
Authors:
- E. GulskiEGE. Gulski
- H.P. BurgerHBH.P. Burger
- G.H. VaillancourtGVG.H. Vaillancourt
- R. BrooksRBR. Brooks
- 1 January 2000
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 7 (1) , 95-101
Abstract
The partial discharge (I'D) aeasureinei~ts on powcr transfortncrs arc studied with IZ view to- ward discrimination and claasificatioii of diffcrcirt discliargc sonrccs. For this purposc digital analysis is applied to power transformers and renctois going through acceptance testing. Fur- thermore, based OH these measurements, PU databases havc been developed to support thc discharge evaluation during iiiduced voltage tests of transformers. Using this technique, a clear distinction is possible betwecn iransforiiwrs showing diffcrcnt discharge behavior.Keywords
This publication has 3 references indexed in Scilit:
- The use of fractal features for recognition of 3-D discharge patternsIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- Digital analysis of partial dischargesIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- Automated recognition of partial dischargesIEEE Transactions on Dielectrics and Electrical Insulation, 1995