Abstract
Since the loss of vital alternating current power and the residual heat removal system (RHRS) during shutdown at Vogtle Unit 1 on March 20, 1990, much attention has been focused on the need to evaluate system performance following such an event in a light water reactor. To evaluate system response following loss of the RHRS, a simplified, transient, nonequilibrium methodology was developed to provide early insights into the accident consequences and identify key phenomenological and system behavior in need of further, more detailed studies.During shutdown, with the reactor coolant system (RCS) at reduced pressure and temperature, inventory reductions are achieved through the introduction of nitrogen into the system. On removal of the man way entries, air can then enter the system. If the RHRS fails under such conditions, the steam generators may be able to be used as an alternate means of decay heat removal provided RCS integrity can be ensured. Moreover, once boiling initiates, RCS pressure incre...