Characteristic Investigation and Overvoltage Suppression of MMC-HVDC Integrated Offshore Wind Farms Under Onshore Valve-Side SPG Fault
- 11 January 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 39 (1) , 1346-1359
Abstract
The valve-side ground fault in the converter station of modular multilevel converter based high voltage direct current (MMC-HVDC) is a serious threat to the security of power systems. Hence, this paper analyzes the most common single-phase-to-ground (SPG) fault characteristics of valve-side faults in onshore converter stations of MMC-HVDC integrated offshore wind farms. The propagation and impact mechanism of onshore SPG fault to offshore HVDC transmission lines, offshore converter station, and wind farms are deduced based on the MMC control principle. Furthermore, an overvoltage suppression strategy based on zero-sequence voltage modulation is proposed. The effect mechanism of this strategy on the transient stability of the system is analyzed. The key parameter of the proposed strategy is also designed considering both the practical engineering requirements and the impact of the system operation. Finally, the theoretical analysis of fault characteristics and the proposed overvoltage suppression strategy are verified by the PSCAD/EMTDC simulation platform. Simulation results not only show good agreement with the theoretical analysis of the fault characteristics, but also prove the effectiveness of the proposed overvoltage suppression strategy.Keywords
Funding Information
- National Natural Science Foundation of China (52022035)
This publication has 32 references indexed in Scilit:
- Analysis of Single-Phase-to-Ground Faults at the Valve-Side of HB-MMCs in HVDC SystemsIEEE Transactions on Industrial Electronics, 2018
- Transient Characteristics Under Ground and Short-Circuit Faults in a ${\pm \text{500}\,\text{kV}}$ MMC-Based HVDC System With Hybrid DC Circuit BreakersIEEE Transactions on Power Delivery, 2018
- Analysis of single-phase-to-ground faults at the valve-side of HB-MMCs in bipolar HVDC systems2017
- Enhanced Independent Pole Control of Hybrid MMC-HVdc SystemIEEE Transactions on Power Delivery, 2017
- Advanced Fault Ride-Through Management Scheme for VSC-HVDC Connecting Offshore Wind FarmsIEEE Transactions on Power Systems, 2016
- Simulation of Startup Sequence of an Offshore Wind Farm With MMC-HVDC Grid ConnectionIEEE Transactions on Power Delivery, 2016
- Characteristic Investigation and Control of a Modular Multilevel Converter-Based HVDC System Under Single-Line-to-Ground Fault ConditionsIEEE Transactions on Power Electronics, 2014
- Operation and Control of a DC-Grid Offshore Wind Farm Under DC Transmission System FaultsIEEE Transactions on Power Delivery, 2013
- Power Flow and Power Reduction Control Using Variable Frequency of Offshore AC GridsIEEE Transactions on Power Systems, 2013
- Research on the fault characteristics of HVDC based on modular multilevel converter2011