HVAC Control System Using Predicted Mean Vote Index for Energy Savings in Buildings
Authors:
- Daniel Fernando Espejel-BlancoDEDaniel Fernando Espejel-Blanco
- José Antonio Hoyo-MontañoJHJosé Antonio Hoyo-Montaño
- Jaime ArauJAJaime Arau
- Guillermo Valencia-PalomoGuillermo Valencia-Palomo
- Abel García-BarrientosAGAbel García-Barrientos
- Héctor Ricardo Hernández-De-LeónHHHéctor Ricardo Hernández-De-León
- Jorge Luis Camas-AnzuetoJCJorge Luis Camas-Anzueto
Open Access
Abstract
Nowadays, reducing energy consumption is the fastest way to reduce the use of fossil fuels and, therefore, greenhouse gas emissions. Heating, Ventilation, and Air Conditioning (HVAC) systems are used to maintain an indoor environment in comfortable conditions for its occupants. The combination of these two factors, energy efficiency and comfort, is a considerable challenge for building operations. This paper introduces a design approach to control an HVAC, focused on an energy consumption reduction in the operation of the HVAC system of a building. The architecture was developed using a Raspberry Pi as a coordinator node and wireless connection with sensor nodes for environmental variables and electrical measurement nodes. The data received by the coordinator node is sent to the cloud for storage and further processing. The control system manages the setpoint of the HVAC equipment, as well as the turning on and off the HVAC compressor using an XBee-based solid state relay. The HVAC temperature control system is based on the Predicted Mean Vote (PMV) index calculation, which is used by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) to find the appropriate setpoint to meet the thermal comfort of 80% of users. This method combines the values of humidity and temperature to define comfort zones. The coordinator node makes the compressor control decisions depending on the value obtained in the PMV index. The proposed PMV-based temperature control system for the HVAC equipment achieves energy savings ranging from 33% to 44% against the built-in control of the HVAC equipment, when operating with the same setpoint of 26.5 grades centigrade.Keywords
Funding Information
- Tecnológico Nacional de México (M00/0327/2017)
- PRODEP (ITHER-18-7934)
This publication has 32 references indexed in Scilit:
- On control of discrete-time state-dependent jump linear systems with probabilistic constraints: A receding horizon approachSystems & Control Letters, 2014
- Automatic Control System for Thermal Comfort Based on Predicted Mean Vote and Energy SavingIEEE Transactions on Automation Science and Engineering, 2014
- Comfort-based fuzzy control optimization for energy conservation in HVAC systemsControl Engineering Practice, 2014
- Development of an energy evaluation methodology to make multiple predictions of the HVAC&R system energy demand for office buildingsEnergy and Buildings, 2014
- Importance of occupancy information for building climate controlApplied Energy, 2013
- Building commissioning: a golden opportunity for reducing energy costs and greenhouse gas emissions in the United StatesEnergy Efficiency, 2011
- Exploiting Kautz functions to improve feasibility in MPCIFAC Proceedings Volumes, 2011
- Use of genetic algorithms to develop an adaptive fuzzy logic controller for a cooling coilEnergy and Buildings, 2010
- Predictive controllers for thermal comfort optimization and energy savingsEnergy and Buildings, 2008
- Comparison of the performance of fuzzy controllers for the management of the indoor environmentBuilding and Environment, 2003