Aspects of Data Models compatibility within Substation hybrid LANs
Authors:
- 16 June 2021
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Abstract
The aim of this paper is to present various communication protocol conversions aspects and Data Models Mapping compatibility among different communications standards used in a power substation network. At one side is IEC61850 and on the other side are legacy protocols such Modbus RTU, IEC 60870-5-103, IEC 60870-5-101, and its extension IEC 60870-5-104 to suit the complete network access. The Data Models Mapping are translated, either by the bay controller or the substation main communication Server, from a hierarchical and tri-dimensional model of IEC 61850 to a linear-plane data models of legacy protocols, and vice versa.Keywords
This publication has 5 references indexed in Scilit:
- The evolution and challenges of modern Distributed Control Systems2020
- Conceptual Design of IoT-Based AMR Systems Based on IEC 61850 Microgrid Communication Configuration Using Open-Source Hardware/Software IEDEnergies, 2019
- Cloud-Assisted IoT-Based SCADA Systems Security: A Review of the State of the Art and Future ChallengesIEEE Access, 2016
- Hybrid Communication Network for the Smart Grid: Validation of a Field Test ExperienceIEEE Transactions on Power Delivery, 2015
- Overview of IEC 61850 and Benefits2006