Open-loop PDCI probing tests for the Western North American power system
Authors:
- 1 July 2014
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 19325517,p. 1-5
Abstract
Poorly-damped electromechanical oscillations are of concern in the western North American power system. Recent development of reliable real-time wide-area measurement systems has enabled the potential for large-scale damping control approaches for stabilizing critical oscillation modes. The current approach being developed is feedback modulation of the Pacific DC Intertie (PDCI). This paper summarizes several years of open-loop actual-system PDCI probing tests. This includes a total of 56 tests conducted in 2009, 2011, and 2012. Test goals are to: 1) evaluate the controllability and robustness of the PDCI with WAMS feedback for damping; and 2) compare actual-system results to model-based transient stability and eigenanalysis studies.Keywords
This publication has 6 references indexed in Scilit:
- PDCI damping control analysis for the western North American power system2013
- Probing Signal Design for Power System IdentificationIEEE Transactions on Power Systems, 2009
- Initial Results in Power System Identification From Injected Probing Signals Using a Subspace MethodIEEE Transactions on Power Systems, 2006
- Model validation for the August 10, 1996 WSCC system outageIEEE Transactions on Power Systems, 1999
- Emergence of a New Swing Mode in the Western Power SystemIEEE Transactions on Power Apparatus and Systems, 1981
- Operating Experience with Modulation of the Pacific HVDC IntertieIEEE Transactions on Power Apparatus and Systems, 1978