Abstract
This paper presents a two-terminal fault-location method which works with unsynchronized phasors. The algorithm is iterative and takes a distributed line model into account. At each iteration, the voltage magnitudes computed from the voltage and current phasors measured at the sending and receiving ends are approximated by two straight lines, and the fault-location estimate is obtained by the intersection point of these two lines. The process ends when the difference between two successive fault-location estimates reaches a threshold stipulated by the user. Since the search process is based on voltage magnitudes, the proposed approach does not require synchronism between the measurements obtained at each transmission-line terminal. The evaluation tests show that the fault-location error of the proposed approach is negligible if the phasors measured at both line ends and the line parameters are accurate. For actual fault conditions, the fault-location error is dependent on the accuracy of the phasor magnitudes and transmission-line parameters.Keywords
This publication has 13 references indexed in Scilit:
- A Two-terminal Fault Location Approach Based on Unsynchronized Phasors2006
- Improved unsynchronized two-end algorithm for locating faults in power transmission lines2004
- New mode domain multiphase transmission line model-Clarke transformation evaluation2002
- An adaptive PMU based fault detection/location technique for transmission lines. II. PMU implementation and performance evaluationIEEE Transactions on Power Delivery, 2000
- Development of an advanced transmission line fault location system. II. Algorithm development and simulationIEEE Transactions on Power Delivery, 1992
- A new fault location technique for two- and three-terminal linesIEEE Transactions on Power Delivery, 1992
- Accurate fault location technique for power transmission linesIEE Proceedings C Generation, Transmission and Distribution, 1990
- An Accurate Fault Locator With Compensation For Apparent Reactance In The Fault Resistance Resulting From Remore-End InfeedIEEE Transactions on Power Apparatus and Systems, 1985
- Development of a New Type Fault Locator Using the One-Terminal Voltage and Current DataIEEE Transactions on Power Apparatus and Systems, 1982
- A New Alogorithm of an Accurate Fault Location for EHV/UHV Transmission Lines: Part I - Fourier Transformation MethodIEEE Transactions on Power Apparatus and Systems, 1981