Degradation of the compression strength of spacers made of high-density pressboard used in power transformers under the influence of thermal ageing
Open Access
- 22 May 2023
- journal article
- research article
- Published by Springer Nature in Cellulose
- Vol. 30 (10) , 6539-6558
Abstract
The structural components inside power transformers are commonly made of high-density pressboard, due to its suitable mechanical and dielectric properties. Among these components are the spacers used in the windings of transformers, which are subjected to compressive loading during operation. The spacers are immersed in dielectric liquid and subjected to high temperatures and chemical reactions during the lifespan of the transformer, which result in the degradation of their dielectric and mechanical properties. The performance and reliability of the power transformer greatly depends on its mechanical integrity, so it is necessary to understand how ageing degrades the mechanical response of the high-density pressboard. In this study, spacers made of high-density pressboard and pieces of copper conductor were immersed in uninhibited paraffinic oil and aged at 150 °C for different periods of time, trying to realistically represent the process suffered by a power transformer during its whole lifespan. The evolution caused by the thermal ageing over some chemical parameters (acidity and moisture content) and dielectric properties (AC breakdown voltage, dielectric dissipation factor, resistivity and degree of polymerisation) of the oil and the pressboard was studied experimentally. Compressive mechanical tests were performed on samples of the aged high-density pressboard, and the compressive stiffness during the ageing process was related with other chemical and dielectric parameters.Keywords
All Related Versions
Funding Information
- Universidad de Cantabria
This publication has 33 references indexed in Scilit:
- Analysis of the micromechanical deformation in pressboard performed by X-ray microtomography2015
- Aging rate of grade 3 presspaper insulation used in power transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Modeling and experimental validation of the mechanical behavior of pressboard2014
- Characterization of aging transformer oil-pressboard insulation using some modern diagnostic techniquesEuropean Transactions on Electrical Power, 2010
- Asset management techniques for transformersElectric Power Systems Research, 2010
- A comparative study of thermal aging of transformer insulation paper impregnated in natural ester and in mineral oilEuropean Transactions on Electrical Power, 2009
- A model for the through-thickness elastic–plastic behaviour of paperInternational Journal of Solids and Structures, 2003
- Plasticity in the Thickness Direction of Paperboard Under Combined Shear and Normal LoadingJournal of Engineering Materials and Technology, 2001
- Degradation of cellulosic insulationin power transformers.Part 3: Effects of oxygen and water on ageing in oilIEE Proceedings - Science, Measurement and Technology, 2000
- An assessment of the physical basis for the application of design criteria for dielectric structuresIEEE Transactions on Electrical Insulation, 1989