Lightning Surge Analysis for Overhead Lines Considering Corona Effect
Open Access
- 25 September 2021
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 11 (19) , 8942
Abstract
Corona discharge characteristics are measured in a corona cage. The difference is found between the q–u curves under double exponential and damped oscillation surges. The behavior of the minor loops is revealed for the q–u curves under positive and negative damped oscillation surges. An extended improvement is made on the traditional approach for modeling of the q–u curves under damped oscillation surges. The extended approach has the capability of describing the complicated trajectory feature of the minor loops. On the basis of the extended approach, an efficient method is proposed for performing lightning surge analysis of overhead lines considering the corona effect. In the proposed method, an overhead line with corona is divided into a certain number of line segments. Each segment is converted into a circuit unit consisting of a non-linear branch and a linear circuit. With these circuit units connected in sequence, a complete equivalent circuit is constructed for the overhead line with corona. The transient responses can be obtained from the solution to the equivalent circuit. Then, the calculated results are compared with the field test results on a test overhead line.Keywords
Funding Information
- National Natural Science Foundation of China (51777007)
This publication has 27 references indexed in Scilit:
- An experimental study on corona q - u curves under non-standard lightning impulsesJournal of Electrostatics, 2016
- Attenuation and deformation characteristics of lightning impulse corona traveling along bundled transmission linesElectric Power Systems Research, 2014
- Multiphase transmission line modeling for voltage sag estimationElectrical Engineering, 2010
- Study of Lightning Surge Overvoltages at Substations Due to Direct Lightning Strokes to Phase ConductorsIEEE Transactions on Power Delivery, 2009
- Lightning impulse corona characteristics of conductors and bundlesIEEE Transactions on Power Delivery, 1997
- Modelling of corona at a high-voltageconductor under double exponential andoscillatory impulsesIEE Proceedings - Science, Measurement and Technology, 1996
- A REALISTIC CORONA MODEL FOR LIGHTNING TRANSIENT STUDIESElectric Machines & Power Systems, 1994
- Evaluation of corona and line models in electromagnetic transients simulationsIEEE Transactions on Power Delivery, 1991
- Studies on modeling corona attenuation of dynamic overvoltagesIEEE Transactions on Power Delivery, 1989
- The surge corona dischargeProceedings of the IEE Part C: Monographs, 1961